Abstract

The roof of a family home introduces important amounts of heat into the house. In Santa Fe city (Argentina), the attic of social family houses is not designed with thermal optimization purposes. In this work, a low Reynolds number k-e turbulent model is computationally implemented to show that a proper selection of constructive parameters of a vented attic leads to a great reduction of the heat transferred from the roof to the ceiling. The main physical consequence of a vented attic is the existence of a convective flow barrier close to the roof that carries important amounts of heat from the attic out to the environment. It is shown that the heat transferred through the ceiling to the interior of the house can be reduced in more than 70 % for summer conditions. Roof pitch and attic volume are also explored.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.