Abstract For the power-flow solution of integrated AC–DC systems, five quantities are required to be solved per converter, against three independent equations available. These three equations consist of two basic converter equations and one DC network equation, corresponding to each converter. Thus, for solution, two additional equations are required. These two equations are derived from the control specifications adopted for the DC link. Depending on the application, several combinations of valid control specifications are possible. A set of valid control specifications constitutes a control strategy. It is observed that the control strategy adopted for the DC link strongly affects the power-flow convergence of integrated AC–DC systems. This paper investigates how different control strategies affect the power flow convergence of integrated AC–DC systems. Sequential method is used to solve the DC variables in the Newton Raphson (NR) power flow model. Seven typical control strategies have been taken into consideration. This is validated by numerous case studies carried out with multiple DC links incorporated in the IEEE 118-bus and 300-bus test systems.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.