Abstract

Abstract On 27 April 1999 a fire test was performed with a 45 m3 rail tank car partially filled with 10 m3 pressurised liquid propane. A CASTOR THTR/AVR spent fuel transport cask was positioned beside the propane tank as to suffer maximum damage from any explosion. About 17 min after fire ignition the propane tank ruptured. This resulted in a BLEVE with an expanding fireball, heat radiation, explosion overpressure, and tank fragments projected towards the cask. This imposed severe mechanical and thermal impacts directly onto the CASTOR cask, moving it 7 m from its original position. This involved rotation of the cask with the lid end travelling 10 m before it crashed into the ground. Post-test investigaiions of the CASTOR cask demonstrated that no loss of leaktightness or containment and shielding integrity occurred.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.