Abstract
In the last decade, several works have been reported for stable and integrating processes to achieve a specified maximum sensitivity. Also, internal model control (IMC) is a popular controller design strategy as it has only one tuning parameter. IMC based controllers are available in literature for time-delayed inverse response processes but none of the reported works provide guidelines for selecting the tuning parameter. In the present work, IMC-PI/PID controllers for time-delayed inverse response processes are reported. To achieve a specified maximum sensitivity in the range of 1.4 to 2.0, set of tuning rules is proposed for the tuning parameter. Normalized form of the transfer functions are used in the present method which simplifies the design procedure. Novelty of the proposed approach is that the user can not only tune the tuning parameter for desired maximum sensitivity, but can also switch from smooth (Ms = 1.4) to tight (Ms = 2.0) control. Simulation results illustrate the effectiveness of the proposed tuning rules.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.