Abstract

We are now developing a new metric of data center power efficiency to fairly evaluate the contribution of each improvement for power efficiency. In order to develop it, we built a testbed of a data center and measured power consumption of each components and environmental variables in some detail, including the power consumption and temperature of each node, rack and air conditioning unit, as well as load on the CPU, Disk I/O and the network. In these measurements we found that there was a significant imbalance of CPU temperatures that caused an imbalance in the power consumption of fans. We clarified the relationship between CPU load and fan speed, and showed that scheduling or rearrangement of nodes could reduce the power consumption of fans. We reduced fan power consumption by a maximum of 62% and total power consumption by a maximum of 12% by changing the scheduling of five nodes, changing the nodes used from hot nodes to cool nodes.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.