Abstract

In this paper, a negative-sequence current differential algorithm using asynchronous positive-sequence voltages is proposed to solve the problem that the negative-sequence current differential algorithm using asynchronous negative-sequence voltages may cause malfunction due to the small magnitude of the negative-sequence voltages. This algorithm using asynchronous negative-sequence voltages is an algorithm for solving erroneous operation due to effects of fault resistance and time synchronization problems of current differential algorithm. And this paper explains why positive-sequence voltage was used, and difference in detection of fault direction at relay point of each algorithm. And then, Each algorithm is tested in an IEC-61850 based centralized protection system environment configured using Real Time Digital Simulator and IEDs(Intelligent Electronic Devices), which are implemented with the MMS-EASE Lite library and Evaluation Modules. The test results show that only the proposed algorithm operate successfully, and therefore the proposed algorithm is appropriate for transmission line backup protection.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.