Abstract
The feature extraction and pattern recognition techniques are of great importance to assess the insulation condition of gas-insulated switchgear. In this work, the ultra-high-frequency partial discharge (PD) signals generated from four types of typical insulation defects are analysed using S-transform, and the greyscale image in time-frequency representation is divided into five regions according to the cutoff frequencies of TE m 1 modes. Then, the three low-order moments of every subregion are extracted and the feature selection is performed based on the J criterion. To confirm the effectiveness of selected moment features after considering the electromagnetic modes, the support vector machine, k-nearest neighbour and particle swarm-optimised extreme learning machine (ELM) are utilised to classify the type of PD, and they achieve the recognition accuracies of 92, 88.5 and 95%, respectively. In addition, the results show that the ELM offers good generalisation performance at the fastest learning and testing speeds, thus more suitable for a real-time PD detection.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.