Abstract
The localization of the dominant harmonic distortion source in the electrical network is one of the practical tasks in the consideration of the power quality in electric power systems. The conventional methods of the estimating of the impacts of the utility and the customer to the harmonic distortion at the network node are the harmonic power flow analysis as well as the correlation analysis of the harmonic voltage and current phasors. The practical use of both methods is discussed below by means of the example of the identification of the dominant harmonic source in the LV supply feeder of an industrial consumer. Based on the analysis carried out it is shown that the direction of harmonic active power flows is a more common and reliable criterion in comparison with the correlation analysis for the identification of dominant harmonic sources in electric power systems.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.