Abstract
In this paper, interarea modes are identified from ringdown frequency data acquired through wide-area measurement systems (WAMSs). These data contain not only an impulse response of interarea modes and noise but also a decaying dc component. The impulse response can be deformed by controlling the power system. An effectual impulse response is determined from a difference sequence between two sets of the data to remove the dc component and the deformation. A modal identification method is developed to minimize the noise of the effectual impulse response through singular value decomposition (SVD) with choice of rank thresholds. The developed method and a conventional Prony method are compared through simulations on the SNR. Kundur’s test system is identified to verify the usefulness of the effectual impulse response. The developed method is applied to identify real power systems from Frequency Monitoring Network (FNET) data.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.