This paper presents a novel method based on higher-order statistics for discrimination between magnetizing inrush and internal fault in power transformers. The distribution characteristics of the sample points of differential currents, under various operation conditions, are firstly investigated and quantified using higher-order statistics. Based on these characteristics, three kurtosis-based indices are defined for distinguishing inrush current from internal fault current. The final discrimination criterion combines these three indices to improve the performance of inrush current identification. Extensive simulation studies and experimental tests verify the effectiveness of the proposed method and its advantages over the conventional second harmonic restraint method.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.