Abstract

This paper introduces novel methods for the identification and location of very high impedance one phase-to-earth faults in medium-voltage (MV) networks in order to improve the electrical safety and reduce the number and duration of outages to customers. The examination is restricted to neutral compensated and isolated MV systems which are the prevailing neutral treatment practices in Europe. The main target of the study was the development of the new method for the identification and location of earth faults up to very high fault resistances. The method is technically applicable in actual use because it utilizes standard measurements available at all 110/20 kV primary substations. No new measuring instruments or devices are needed. The major algorithm is based on the calculation of the fault resistance for every MV feeder. Field experiments in real networks have also been conducted for testing the methods. The indication method presented can identify and locate faults approximately up to 100–200 k $\Omega$ .

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.