Abstract

Many researchers pay attention to the problem of the distortion electric power. The known theoretical results that are reflected in the acting standards are reasonably criticized in the part of the distortion power generation by current and voltage of different frequencies. The paper deals with the approach based on the order of generation of instantaneous electric power components depending on the combination (sum or difference) of current and voltage frequencies. The analytical expressions for the instantaneous electric power components of a harmonic current circuit consisting of a capacitor, an inductance coil and a resistor connected in series are obtained. With this purpose in view, two components – active and reactive – are singled out from the obtained four components of instantaneous power, as well as the orthogonal power components oscillating with double frequency. It is demonstrated that the sum of the squares of the active and reactive components and the sum of the squares of the mentioned orthogonal components coincide and are equal to the total (apparent) power. The used method is developed for the general case of polyharmonic current and voltage. In this case, it is observed that the active and reactive power components can be singled out from the instantaneous power components as orthogonal quadrature components of zero frequency. Though, it is impossible to single out the apparent power. Two numerical experiments with periodic current and voltage, containing three harmonics each, were carried out. The acting values of currents and voltages in each of the experiments were assumed equal. In this case, the amplitudes of the second and the third harmonics exchanged their positions. This example demonstrates that the integral indices of the apparent power and the distortion power, calculated by conventional methods, proved to be the same in both cases, which is incorrect. Under the same conditions, such instantaneous power components whose values turned out to be different for each of the experiments are found among the proposed instantaneous power components. As a result, it is proposed to use a root-mean-square value of the mentioned components for the assessment of the distortion degree in relation to the root-mean-square value of the instantaneous power

Highlights

  • Electrotechnical and electromechanical systems and complexes, to solve the problems related to the conversion of electric energy into other types of energy, one uses energy or power balance equations

  • The average value of power is used as an accounting index for direct current networks, the values of the active and reactive power are used for alternating current networks [1, 2]

  • Electric power systems are used for the generation and transmission of the energy that is primarily determined for the electric circuit by active power: 1 t0 +T

Read more

Summary

Introduction

Electrotechnical and electromechanical systems and complexes, to solve the problems related to the conversion of electric energy into other types of energy, one uses energy or power balance equations. The balance equation is formed according to the corresponding values averaged at a certain time period. The average (at a certain period of time) value of power is used as an accounting index for direct current networks, the values of the active and reactive power are used for alternating current networks [1, 2]. The problems of determining the power components reflecting the nature and level of electric energy distortion are topical

Literature review and problem statement
The aim and objectives of the study
Conclusions