Abstract

The paper presents identi cation results of deformation processes within power oil transformers where according to dissolved gas analysis investigation results partial discharges took place. The original method worked out for analysis of acoustic emission signals recorded within tested transformer and particularly maps of ADC descriptors have been applied. Analysis has been carried out within chosen frequency bands in order to distinguish signals coming from di erent sources (among other things partial discharges, Barkhausen's e ect, circulation of the oil, and outer acoustic sources). One source of partial discharges has been identi ed within the tested transformer as a result of analysis of acoustic emission signals.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.