Abstract
Underground residential distribution (URD) power cables are aged due to electrical, thermal, mechanical and environmental stress during their service. For utilities, the recent dielectric conditions of the cables are of much interest. Fast Fourier Transform Analysis of the impulse wave propagating in URD is one of the online non-destructive methods to estimate the cable insulation condition. In this study, the radial URD system with aged cable sections was modeled using EMTP for transient studies. A switching transient was simulated in the energized model of the URD system. Based on the Frequency Spectrum of the voltages at different points in the model URD, an aged cable section identification methodology using feature classification is presented in this paper.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.