Abstract

The concept of integrating PV panels into traditional ETICS facades has been developing for several years. Problems concerning the options for passively controlling the temperatures of PV panels with PCM and directing excess moisture out of the wall via diffusion channels have been previously studied theoretically. During this study, real wall-scale experiments were conducted to test the thermal and hygrothermal performance of the wall system in an extreme climatic environment, as well as in a real outdoor environment in Tallinn, Estonia. Finally, a simulation model was calibrated according to the measured data. It was found that in case of test walls with diffusion channels, it was possible to keep the moisture content of PCM mortar under 0.11 m3/m3. Excess water drained out via channels leading to the external environment. Without diffusion channels, the moisture content rose as high as 0.18 m3/m3. Both the experiments and hygrothermal modelling showed that the high moisture content of PCM mortar, caused by water leakage, dropped to 0.08 m3/m3 over 10 solar cycles as moisture escaped via the diffusion channels. PCM mortar with a moisture content of 0.08 m3/m3 endured extreme rain and freeze-thaw cycles without visual damage, and PV panels retained their electrical production capabilities.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.