Abstract

This paper deals with the problem of reactive power and harmonics in a standard medium-voltage (MV) distribution network. It proposes a simple and inexpensive solution to enhance power quality when a particular connection to the high-voltage transmission network is required. It presents the design of a hybrid active filter topology connected to the MV level of a power distribution system. Its main task is to regulate a 132-kV voltage level. Reconfiguration of the power delivery network imposes new constraints in a distribution substation so that the reactive compensation should be increased. The topology of a shunt hybrid active filter is analyzed. It is built with the series connection of a passive filter and a low-rated active filter. The proposed filter is directly connected to a 13.8-kV level with no need of a step-down transformer. The possibility of different levels of reactive power compensation is implemented. The proposal shows very good performance for different load demands.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call