Abstract

This study focuses on a hybrid liquid desiccant air-conditioning system consisting of a conventional liquid desiccant system and a vapour compression heat pump. The hybrid liquid desiccant air-conditioning system is expected to enhance the system efficiency of a conventional liquid desiccant system. In this study, the liquid desiccant is aqueous solution of lithium chloride and the refrigerant of the vapour compression heat pump is R407C. The main feature of this system is that the absorber and regenerator are integrated with the evaporator and condenser respectively. The performance evaluation test is conducted to obtain the primary data. Additionally, the improvement method for the system efficiency is discussed by the mathematical calculations. As a result, the system can dehumidify 5.9 g/kg(DA) under the conditions of summer in Tokyo, Japan. Then, the calculation results show that COPs can become higher by improving the compressor isentropic efficiency and the temperature efficiency of solution heat exchanger.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.