Abstract
Based on the system model of hybrid desiccant cooling system using condensing heat as the regeneration source, the solution is given to investigate the system characteristic. The result showed that, when the outdoor air humidity ratio is below 18.5g/kg and indoor dehumidification load is below 1.5kg/h, the energy consumption of this system is lower than the enthalpy recovery air-conditioning system. If not, due to the high energy consumption of electrical heating, the desiccant wheel using condensing heat and electrical heat is not suitable for the humid areas.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.