Abstract

This study addresses fault identification in differential protection of a V/x-type traction transformer used in a high-speed railway. To quickly and accurately identify an internal short circuit in a traction transformer, a hybrid algorithm is developed that combines intrinsic mode function (IMF) energy entropy with the correlation dimension from chaos theory. IMF energy entropy and correlation dimension are sufficiently fast and sensitive to reflect the dynamic changes in the differential-current signal from the traction transformer using different metrics; thus, this hybrid method can effectively identify an internal short circuit and magnetising inrush. Real-time simulations and actual measurements of faults illustrate the validity of the proposed method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.