Abstract

The ac side current of a line commutated converter(LCC) high voltage direct current (HVDC) is characterized by highly non-sinusoidal waveform. If the harmonic current is allowed to flow in the connected ac network, it may cause unacceptable levels of distortion. Therefore, ac side filters are required as part of the total HVDC converter station, in order to reduce the harmonic distortion of the ac side current and voltage to acceptably low levels. The ac filters are also employed to compensate the requested reactive power because LCC HVDC also consume substantial reactive power. Among different types of filters, triple-tuned filters have been widely utilized for HVDC system. This paper presents two design methods of triple-tuned filter; equivalent method and parametric method. Using a parametric method, in particular this paper proposes a design algorithm for a triple tuned filter. Finally, the performance of the design algorithm is evaluated for a 250kV HVDC system in Jeju island. The results cleary demonstrate the effectiveness of proposed design method in harmonics reduction.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.