Abstract

Hybrid ac/dc transmission can increase the power transfer capability of long ac transmission lines. High voltage dc (HVDC) converters are needed, and the line-commutated converter (LCC) is used considering the dc fault current controllability. However, zero-sequence current can be generated due to the coupled transmission lines, and it will flow into the HVDC converters as a fundamental frequency current component on dc side (i60). The LCC will convert i60 to dc current components on the ac side, which may cause potential converter transformer saturation. This paper analyzes the influence of coupled transmission lines on i60 and the converter transformer saturation and proposes two possible solutions to avoid converter transformer saturation. The simulation results verify the effectiveness of the proposed methods.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.