Abstract

We have studied the operation of the circuit breaker for 15 kV DC power grid with the combination of the breaker and the HTS Fault Current Limiter (FCL). The HTS FCL limits the fault current by introduce of the impedance under the fault condition, so the circuit breaker with the HTS FCL module can be expected to be able to break the higher prospective fault current successfully. As an attached module to the DC circuit breaker, we performed a design work for a DC resistive HTS FCL module with SuNAM's REBCO conductor with the stainless-steel stabilizer. Considering the operation delay time of the DC circuit breaker, the HTS FCL module should generate a proper impedance for 16 milliseconds at most without any damages. To verify the design results, we designed and make scaled-down model of the HTS FCL module. We also carried out the DC short-circuit test to check the feasibility and the fault current limiting characteristics of the suggested model.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.