Abstract

This study focuses on a compact Vacuum Circuit Breaker for nominal voltage of 72.5 kV, nominal current of 2000 A and short circuit current of 31.5 kA. The dielectric conception of the vacuum interrupter (VI) is based on: - Standard dielectric criteria including the effect. - A multiple floating shield configuration which reduces risk of total breakdown due to partial breakdown between contacts and shield. - A maximum electrical field on the contact surface that points towards the floating shield hence reducing the effective area of the contacts facing each other. All tests have been performed on a specially designed single-phase circuit breaker pole-unit equipped with a low energy spring type mechanism. Interruption performance was confirmed in direct tests. The CB pole was proved to be restrike-free as defined for class C2. Dielectric tests in new condition and after interruption tests confirmed the announced ratings. These tests confirm the feasibility of this HV-CB with 25% more compact VI's based on the outlined dielectric conception.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.