Abstract

This paper provides the electrical equivalent circuits of high-resistance grounded (HRG) power systems other than the delta-wye-connected utility power supply transformer included in Part I of this paper. This paper also provides the HRG of a medium-voltage generator for connection to an industrial power system and to a utility power system, and this paper discusses a line-ground fault with fault resistance. Three-line diagrams of ungrounded power systems are also included to illustrate the HRG application and its effect on the ground fault current during the line-ground fault. The damage at the fault location is based on the assumption that the fault remains a line-ground fault until it is cleared by appropriate ground fault protection relays. The fault resistance and the fault current that have an effect on the damage at the fault location are included. This paper provides guidance to update the current edition of the IEEE STD. 142, with respect to HRG systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.