Abstract

In this paper, an ex-post analysis based on Higher-Order Statics (HOS) has been proposed for characterizing voltage dips (VDs) recorded in the Italian distribution network by the research monitoring system QuEEN, managed by RSE. HOS basically consists in a signal waveform compression: by considering the signal as a probability distribution function, it can be approximated with its statistical moments; in this work the second (variance), the third (skewness) and the fourth (kurtosis) order moments have been considered. This technique has been applied on a set of waveforms associated to events recorded by the QuEEN monitoring system. The associated VDs have been characterized in terms of residual voltage and duration; moreover, by considering the behavior of the kurtosis and skewness also the “true” and “false” VDs can be detected. In this way an efficient and effectiveness processing technique can be implemented for future developments of the QuEEN functionalities.