Abstract

The simulation of the modes of power supply systems of different voltages, with a transformer carrying linear and non-linear loads and a capacitor bank, has been implemented. The dependences of the capacitors overload by current and the coefficient of harmonic voltage components on the capacitor bank capacity within the operating range of the transformer total load by linear and non-linear loads have been obtained. For the systems under consideration, upon a daily variation in the capacitor bank linear load and capacity, it is virtually impossible to eliminate the capacitors overload by higher harmonic currents and observe regulatory voltage quality requirements. Anti-resonant chokes installation in the capacitor bank circuits reduces the overload of capacitors to a permissible value, and brings up the coefficient of harmonic voltage components to values that took place in the absence of the capacitor bank.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.