Abstract

Aiming at the problems of fuel tank rupture and explosion caused by the internal discharge during the operation of HVDC converter transformers, the test principles and methods for simulating the failure of the converter on-load tap-changer, bushing riser and body were discussed. The arc test model was designed and manufactured. The arc test with a rated current of 25kA and a fault cumulative energy value of 1.46MJ~13.89MJ was carried out. The laws of current, arc voltage and cumulative energy in the dynamic development process of arc discharge fault were revealed. The real test data and test analysis methods are provided for the anti-explosion design of the converter transformer, the function verification of the quick pressure relief device and the analysis of the cause of the arc fault.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.