Abstract
High-impedance faults (HIFs) in electrical power distribution systems produce a very random, non-linear and low-magnitude fault current. The conventional overcurrent (OC) relaying-based distribution system protection schemes find difficulty in detecting such low-current HIFs. In this study, a simple two criteria-based protection scheme is proposed for detection and isolation of HIFs in multi-feeder radial distribution systems. It utilises one-cycle sum of superimposed components of residual voltage for HIF detection and the maximum value of one-cycle sum of superimposed components of negative-sequence current for faulted feeder identification. The performance of the proposed scheme is evaluated for a wide variety of possible test cases by generating data through power systems computer-aided design/electro-magnetic transient design and control software. Results clearly show that the proposed scheme can assist conventional OC relay for detection and isolation of HIFs in distribution systems with any grounding connections in a more reliable and faster way.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.