Abstract

This paper studies the experimental results of the quasi-state high field dc conduction current, and changes occuring in the molecular structure of aged transformer oil, sampled from EHV transformer operating for the last five years. Aged oil was compared with fresh transformer oil and liquid paraffin. It was found that aged oil exhibits higher conduction than both of the other oils through 600 seconds of field application. However, no molecular changes were detected using different techniques of spectroscopy such as GC; UV; IR and NMR. Metallic impurities were found to be of the same order but the acidity increased manifolds to that of fresh oil.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.