Abstract

A hierarchical fuzzy logic controller (FLC) is applied to control the water level in an analytical simulation using a simplified advanced boiling water reactor model. To reduce the control effort of the feedwater pump, the linguistic variable, change in pressure, was adopted. Four linguistic variables were used for the FLC design, and the number of control rules became large if the conventional FLC design method was used. Using a hierarchical rule structure reduces the total number of control rules and thus the final decision tables. To reduce the design effort, two methods were separately developed for fine-tuning. One tunes the scaling factors using an optimization method, and the other tunes the control rules using a method similar to a fuzzy model reference control. The simulation results show that the performance of the hierarchical FLC is comparable to that of the proportional-integral controller, but use of the designed controller results in a shorter settling time.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.