Abstract
A minitype ground source heat pump (GSHP) system was designed and installed in the green energy building of Shanghai Jiao Tong University for the purpose of satisfying the thermal environment of a meeting room with the covered area of 180m2. The rated cooling capacity of the heat pump is 22.3kW with the electricity consumption of 5.3kW. Correspondingly, the rated heating capacity and electricity consumption in heating mode is 29.5kW and 6.9kW, respectively. The ground heat exchanger consists of 9 vertical boreholes. There is a single U-tube with the diameter of 32mm in each borehole. The whole length of the U-tube is 580m. The experimental investigation was carried out in both cooling mode and heating mode. After one year, the average temperature of soil was about 18°C, which is nearly the same as the original soil temperature. The experimental results are instructive to the design and operation of GSHP systems in Shanghai and other cities with similar climatic feature.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.