Abstract

The theory of liquid-coupled indirect heat exchanger systems has been studied to ascertain optimum criteria with respect to the coupling-liquid flow rate and the distribution of total heat transfer area between the hot-side and cold-side exchanger units in the case of counterflow arrangement. The optimum coupling-liquid capacity rate is derived and given as a function of the over-all capacity rate ratio and the Ntu ratio between the two exchanger units. For this optimum liquid capacity rate together with the proposed over-all number of transfer units, it is shown that the over-all heat transfer effectiveness of the liquid-coupled system can be expressed in the ordinary form for individual exchanger units in true counterflow.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.