Abstract
This study examines several effects, including the piezofan positions, and piezofan arrangements, as well as piezofan height, on the heat transfer enhancement of two typical types of vertical heat sink. Either 30-mm-high or 10-mm-high heat sink having 11 plate-fins or 100 square pin-fins is tested with a running piezofan. The piezofan having Mylar blade is either vertically or horizontally placed above the heat sinks vibrating with resonant frequency of 31 Hz and tip mean-to-peak amplitude of 7.2 mm. The heat transfer coefficient is measured at five different fan locations with fan heights of 12 mm and 16 mm. Results show that the piezofan located at x/L = 0.5 usually performs the highest heat transfer enhancement for a given heat sink, while piezofan located at x/L = 1 usually shows the worst heat transfer enhancement. Depending on the fan arrangements and positions, heat transfer coefficient of the present 10-mm-high plate-fin heat sink shows 1.2 – 2.4 times higher than that under natural convection, while the enhancement factor ranges from 1.1 to 2.6 for 10-mm-high pin-fin heat sink.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.