Abstract

An experimental investigation was conducted to determine the heat transfer characteristics of HCFC-22 for a two-phase double tube connected to a heat pump. This study focussed on the forced convection boiling heat transfer of small flow rate in a double tube. It was clarified that the quality at the dry-out point increases as mass velocity increases, and that the heat transfer coefficient of two-phase flow is about 30 times as large as that of the liquid single-phase laminar flow. Furthermore, it was found that the heat transfer performance of the double tube is superior to that of a single tube.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.