Abstract

It is common for loop heat pipes to experience start-up problems under low thermal loads. The start-up characteristic of a loop heat pipe with flat evaporator was investigated experimentally in this study. A bypass line was attached to the evaporator to alleviate the difficulties associated with startup. Axial grooves were provided in the flat evaporator to serve as a vapor passage. The evaporator and condenser had dimensions of 40 mm (W) by 50 mm (L). Coolant paths were machined inside the condenser. The inner diameters of liquid and vapor transport lines were 2.0 mm and 4.0 mm, respectively and the length of the two lines was 0.5 m each. The thermal load range was up to 80 W using methanol as a working fluid with the condenser temperature of 10°C at horizontal position. The results showed that a minimum thermal load for the startup was lowered by 37% when the bypass line was employed. However, a periodical performance variation was observed once the startup was achieved under very low thermal loads.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.