Abstract

In this study, condensation of pure refrigerant R134a vapor inside a smooth vertical tube was experimentally investigated. The test section was made of a copper tube with inside diameter of 7.52 mm and length of 1 m. Experimental tests were conducted for mass fluxes in the range of 20–175 kg/m2s with saturation pressure ranging between 5.8 and 7 bar. The effects of mass flux, saturation pressure, and temperature difference between the refrigerant and tube inner wall (ΔT) on the heat transfer performance were analyzed through experimental data. Obtained results showed that average condensation heat transfer coefficient decreases with increasing saturation pressure or temperature difference (ΔT). In addition, for the same temperature difference (ΔT), heat can be removed from the refrigerant at a higher rate at relatively low pressure values. Under the same operating conditions, it was shown that average condensation heat transfer coefficient increases as mass flux increases. Finally, the most widely used heat transfer coefficient correlations for condensation inside smooth tubes were analyzed through the experimental data. The best fit was obtained with Akers et al.'s (1959) correlation with an absolute mean deviation of 22.6%.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.