Abstract

AbstractIn recent years, the requirement for the reduction of energy consumption has been increasing to solve the problems of global warming and the shortage of petroleum resources. A latent heat recovery type heat exchanger is one of the effective methods for improving thermal efficiency by recovering latent heat. This paper describes the heat transfer and pressure loss characteristics of a latent heat recovery type heat exchanger having straight fins (fin length: 65 mm or 100 mm, fin pitch: 2.5 mm or 4 mm). These were clarified by measuring the exchange heat quantity, the pressure loss of the heat exchanger, and the heat transfer coefficient between the outer fin surface and gas. The effects of fin length and fin pitch on heat transfer and pressure loss characteristics were clarified. Furthermore, equations for predicting the heat transfer coefficient and pressure loss which are necessary for heat exchanger design were proposed. ©2007 Wiley Periodicals, Inc. Heat Trans Asian Res, 36(4): 230– 247, 2007; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/htj.20153 Copyright © 2004 Wiley Periodicals, Inc.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call