Abstract

An experimental study on the air-side heat transfer and pressure drop characteristics for brazed aluminum heat exchangers with multi-region louver fins and flat tubes was conducted. A series of tests were conducted for heat exchangers with different numbers of louver regions at the air-side Reynolds numbers of 400–1600 based on the louver pitch. The air-side thermal performance data were analyzed by using the effectiveness-NTU method. The characteristics of the heat transfer and pressure drop for heat exchangers with different geometry parameters were presented in terms of the Colburn j factor and Fanning friction f factor as function of the Reynolds number.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.