Abstract
Steam generation is an essential process in steel production. Saturated steam is used in the cold-rolling mills of sample steel company to raise the acid pool temperature. The studied water-tube boiler had a rated saturated steam generation capacity of 47 tons per hour. This study used energy and exergy balance equations for each of the components in the cycle to calculate exergy efficiency and irreversibility rate. Results from the exergy analysis along with the exergy dissipation rate of the cycle were obtained. Based on the literature results, it was recommended to increase the input air temperature by means of a preheater. First, the exergy dissipation in the boiler was reduced by 68 kJ kg−1 with the installation of an economizer. The most important cause of exergy destruction was then presented, and some recommendations were provided on how to increase the temperature of the makeup water in order to increase the boiler efficiency and exergy.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.