Abstract

The effect of wall axial conduction on the heat transfer in a concentric tube heat exchanger is examined for the inner flow laminar flow regime. The procedure used for the current analysis combines the analytical solution for the inner fluid with a numerical approximation for the wall conduction and has the capability of handling the temperature variation for the outer fluid. Both parallel and counterflow cases are evaluated for the analysis, and results are presented in terms of the axial variations of fluids and wall temperatures. Effects of the heat capacity rate ratio of the fluids on the temperature variations and on the mean heat flux are also pointed out. The effect of the exchanger length is included for the analysis. It is concluded that the total heat transfer between the fluids is greatly influenced by the wall axial conduction for the counterflow arrangement and is not ignorable when the heat capacity rate ratio of fluids are smaller than unity.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.