Abstract

Coolers are the most relevant components of absorption chiller systems regarding electricity and water consumption as well as operational costs, space requirement, and noise emission. While evaporative cooling towers can supply lower temperatures, package type dry coolers are significantly cheaper in investment, operation and maintenance. In the last few years, single effect absorption chillers have been developed to operate with dry coolers. In a field test 25 chillers were tested in 16 different locations throughout Germany. Using dry coolers instead of wet coolers facilitates the overall installation. Project results show the energy efficiency potential of absorption chillers in combination with dry coolers. Three strategies reduced the electrical energy consumption by 70 % on average, without negative side effects for absorption chillers. The annual specific electricity demand of 0.028 kWel/kWth,0 was even lower than typical values for wet cooling towers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.