Abstract

Domestic hot water (DHW) system energy losses are an important part of energy consumption in newly built or in reconstructed apartment buildings. To reach nZEB or low energy building targets (renovation cases) we should take these losses into account during the design phase. These losses depend on room and water temperature, insulation and length of pipes and water circulation strategy. The target of our study is to develop a method which can be used in the early stages of design in primary energy calculations. We are also interested in how much of these losses cannot be utilised as internal heat gain and how much heat loss depends on the level of energy performance of the building. We used detailed DHW system heat loss measurements and simulations from an nZEB apartment building and annual heat loss data from a total of 22 apartment buildings. Our study showed that EN 15316-3 standard equations for pipe length give more than a twice the pipe length in basements. We recommend that for pipe length calculation in basements, a calculation based on the building’s gross area should be used and for pipe length in vertical shafts, a building’s heating area-based calculation should be used. Our study also showed that up to 33% of pipe heat losses can be utilised as internal heat gain in energy renovated apartment buildings but in unheated basements this figure drops to 30% and in shafts rises to 40% for an average loss (thermal pipe insulation thickness 40 mm) of 10.8 W/m and 5.1 W/m. Unutilised delivered energy loss from DHW systems in smaller apartment buildings can be up to 12.1 kWh/(m2·a) and in bigger apartment buildings not less than 5.5 kWh/(m2·a) (40 mm thermal pipe insulation).

Highlights

  • Pipe heat losses in low-energy or nZEB apartment buildings can be more than 10% of the entire primary energy consumption

  • At this point in time, domestic hot water (DHW) and DHW circulation energy consumption heat losses are based on the volume of water consumption

  • Pipe heat loss calculations in the reference building showed that the difference between thermal insulation levels on pipes did not affect how much heat loss from pipes can be utilised as internal heat gain;

Read more

Summary

Introduction

Zero energy (nZEB) apartment buildings have a relatively higher share of energy use for domestic hot water (DHW) because of reduced heat loss from the wellinsulated building envelope, the use of ventilation heat recovery and LED lighting systems. DHW energy consumption can be divided between energy used to heat the water and energy consumed by system losses. Bøhm and Danig showed [1] that in apartment buildings the heat losses from the hot water system correspond to approximately 65% of the energy consumption for domestic hot water and the cause of these heat losses should be further investigated. Gassel [3] showed that if the DHW circulation is constantly in operation, this equates to 15 kWh/m2 ·a energy consumption, the circulation share being

Objectives
Methods
Results
Discussion
Conclusion