Abstract
Heat flux data from a series of controlled experiments involving a 2 m diameter, wind-blown pool fire are examined to highlight the difficulties involved in conducting heat flux measurements in a realistic, large-scale, hydrocarbon-fueled fire. Data were taken at several locations along the ground near the fire. At each location, three different heat flux sensors were positioned together: a Gardon gage, a directional flame thermometer (DFT) and a Sandia heat flux gage (HFG). Methods were first developed to correct measured values of heat flux for the slight differences in gage location relative to the fire. The remaining discrepancies between the values of heat flux measured by the different gages were then used to highlight uncertainties in heat flux measurements due to differences in gage surface temperature, in gage thermal response to the inherent modes of heating involved in the large hydrocarbon fire environment, and in conduction losses from the gage sensor plates. The importance of these sources of discrepancy varied depending on the magnitude of the measured heat flux and on whether the gages were located in a radiation-dominated or mixed radiative-convective environment within the fire.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.