Abstract

An experimental facility was developed to investigate the nonboiling heat transfer performance of water spray cooling. The effects of mass flux and wall temperature on heat transfer coefficient and heat flux were experimentally studied. It was found that heat transfer coefficient increased with the increasing of mass flux and wall temperature. Generalized correlations were developed for the Nusselt number related to wall temperature and the average Nusselt number as a function of the spray Reynolds number and the nondimensional temperature with an absolute error of 4% and 15% when the Reynolds number is more than 440. Compared with the data of Oliphant et al., it was observed that the usage field of the correlations could be extended to Reynolds number greater than 240.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.