Abstract

A model is proposed to analyze the heat transfer of deep borehole heat exchanger (DBHE)arrays. Based on this, a dimension reduction algorithm is proposed for the numerical simulation of heat transfer of DBHE arrays, which can improve calculation speed by several orders of magnitude compared with that by the CFD software. An index of heat extraction capacity (HECI) is adopted to evaluate the heat extraction capacity of DBHE arrays. The influence of borehole spacing, operation time, annual heating duration, terrestrial heat flow rate, borehole depth, soil thermal parameters, pipe diameter and circulating fluid flow rate on DBHE array heat extraction capacity and its attenuation are analyzed. The results show that the borehole spacing, operation time, and annual heating duration all have apparent influence on DBHE array heat extraction capacity and its attenuation rate, while the others only have apparent influence on the heat extraction capacity. According to the calculation results, when the DBHE arrays have a service lifetime of 20–50 years, the recommended borehole spacing range is 40–70 m.