Abstract
Absorption refrigeration cycle can be driven by low-grade thermal energy, such as solar energy, geothermal energy and waste heat. It is beneficial to save energy and protect environment. However, the applications of traditional absorption refrigeration cycle are greatly restricted because they cannot achieve low refrigeration temperature. A new absorption refrigeration cycle is investigated in this paper, which is driven by low-grade energy and can get deep low refrigeration temperature. The mixture refrigerant R23+R134a and an absorbent DMF are used as its working fluid. The theoretical results indicate that the new cycle can achieve −62℃ refrigeration temperature when the genera- tion temperature is only 160℃. This refrigeration tempera- ture is much lower than that obtained by traditional absorp- tion refrigeration cycle. Refrigeration temperature of −47.3 has been successfully achieved by e ℃ xperiment for this new cycle at the generation temperature of 157℃, which is the lowest temperature obtained by absorption refrigera- tion system reported in the literature up to now. The theo- retical and experimental results prove that new cycle can achieve rather low refrigeration temperature.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.