Abstract
In this study, a control system is presented that is devised to increase measurement precisions within a prototype high voltage DC resistive divider (HVDC-RD). Since one of the major sources of measurement errors in such devices is the self heating effect, a system controlling the temperature within the high voltage DC resistive divider is devised so that suitable and stable temperature conditions are maintained that, in return, will decrease the measurement errors. The resistive divider system is cooled by oil, and PID and neural network (NN) controllers try to keep the temperature within the prescribed limits. The system to be controlled exhibits a nonlinear character, and therefore, a control approach based on NN controllers is proposed. Thus, a system that can fulfill the various requirements dictated by the designer is constructed. The performance of the NN controller is compared with that of the PID controller developed for the same purpose, and the values of the performance indices indicate the superiority of the NN controller over that of the classical PID controller.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.