Abstract
The heat-mass transfer and pressure drop performances during the dehumidification of moist air flowing between plate fin and tube heat exchangers which are mainly used in air conditioners were investigated experimentally. The experimental results revealed the following. The heat transfer performance with condensation was equal to that without condensation, in consideration of dehumidified water on the surface of a heat exchager. The analogy between heat and mass transfer under dehumidification was not completely substantiated. The mass transfer coefficient is smaller than that of theoretical analogy.
Published Version (Free)
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: TRANSACTIONS OF THE JAPAN SOCIETY OF MECHANICAL ENGINEERS Series B
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.