Abstract

Numerous problems can occur with liquid oxygen delivery systems, in part because of the complexities of such systems. These systems must comply with guidelines of the Joint Commission on Accreditation of Hospitals. During the past year, 18 major problems with the liquid oxygen delivery system have occurred at the authors' hospital. Five times, false alarms have resulted from calibration drift in line pressure sensors. Thrice, excessive depletion of the reverse supply has occurred because of pressure imbalance between the main and reserve systems. Twice, excessive depletion of the reserve supply occurred owing to failure of the vacuum seal on the reserve supply vessel. Eight other potentially serious mishaps have also been reported. These problems, which are inherent in liquid oxygen delivery systems, are for the most part preventable.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.