Abstract

The investigation of the direct current (dc) bias effect on single phase power transformer through their harmonics performance is present in this paper. The experimental study is done by the dc bias current injected simultaneously with alternating current (ac) source to primary winding of transformer. The input ac voltage to primary winding is maintained constant during investigation and the dc currents increased gradually. Compare to pure ac power applied, the results show that the waveforms distorted when the dc bias exist. The pulsated waveforms are pushed to half cycle in which the bias current is in the same direction as magnetizing current (unsymmetrical pulsated) and even harmonics are significant.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.